On 27 April 2010, a laboratory found 1,281 µL/L of dissolved hydrogen in the synthetic ester of a 3.5 MVA, 20 kV distribution transformer. The unit was barely two years old. It had a sealed tank and flame-resistant synthetic fibre winding insulation. By June the hydrogen concentration had risen to 1,456 µL/L, while the methane concentration had fallen from 319 to 161 µL/L.
We know what the service engineers eventually found because the IEEE working group published the gas results alongside the inspection findings. The windings showed evidence of partial discharge. Would the April sample alone have justified electrical testing? The figures below come from Annex H.2, Tables H.5 and H.6 of the 2014 IEEE guide.
IEC 63585:2026 gives operators guidance on dissolved gas analysis (DGA) in natural and synthetic esters. The April result illustrates a distinction that matters in service. The hydrogen concentration gave the operator grounds to investigate. Identifying a plausible fault from the proportions of the other gases was a separate decision. Scope of IEC 63585:2026.
On this page (6 sections)
- What did the April sample tell the operator?
- How would the offshore and traction fleet criteria read the same sample?
- How much acetylene could the reported zero conceal?
- Where do clause 5.3 and Annex B fit?
- Why request an electrical partial-discharge test?
- Natural esters at 120 °C: why the same ratio can move 161-fold
What did the April sample tell the operator?
| Sample date | Hydrogen H₂ | Methane CH₄ | Ethylene C₂H₄ | Acetylene C₂H₂ |
|---|---|---|---|---|
| 27 April 2010 | 1,281 | 319 | 1 | 0 |
| 9 June 2010 | 1,456 | 161 | 1 | 0 |
Clause 5.1(b) of IEC 63585 uses hydrogen to illustrate how investigation triggers vary between assessment schemes. Its example spans 50 to 400 ppm by volume. At 1,281 µL/L, the April result exceeded even the upper end of that range. Choosing a trigger within it would have made little difference to the decision to investigate. None of those figures alone tells an operator whether a transformer can remain in service.
The IEEE authors plotted the samples on the Duval triangle for synthetic ester. The coordinates are the percentages of methane, ethylene and acetylene in the sum of those three gases. Methane accounted for 319 of 320 µL/L in April and 161 of 162 µL/L in June. Both points fell close to the methane vertex, in the partial-discharge zone. A partial discharge bridges only part of the insulation and can recur while the transformer continues to withstand the applied voltage. Selecting a Duval diagram for the fluid and equipment.
Hydrogen does not enter that triangle. It rose by 175 µL/L between samples while methane fell by 158 µL/L. As a result, the methane-to-hydrogen ratio fell from 0.249 to 0.111. An engineer given only the two nearly coincident points would have missed that change.
There is a discrepancy worth resolving before calculating a gas generation rate. The dates printed in IEEE Table H.5 are 43 days apart, but the interval column gives 32 days. The same hydrogen increase works out at 4.1 or 5.5 µL/L per day, respectively. Before using either rate to set the next sampling date, I would check the original sampling records.
How would the offshore and traction fleet criteria read the same sample?
Ivanka Atanasova-Höhlein and Carolin Schütt studied synthetic ester in 912 offshore wind transformers and 130 aramid-insulated traction transformers. In their 2022 CIGRE paper they proposed three simultaneous conditions for identifying partial discharge in the fleets they studied. Hydrogen had to reach at least 100 µL/L, methane divided by hydrogen had to be 0.2 or less, and acetylene divided by ethylene had to be 0.1 or less. Applying their rule to the 2010 distribution transformer is a retrospective comparison. Atanasova-Höhlein and Schütt, CIGRE paper A2-11064, Table 5.
The April sample easily met the hydrogen condition. At 1,281 µL/L of hydrogen, however, the methane concentration would have had to stay below about 256 µL/L to satisfy the second condition. The laboratory measured 319. The Duval result therefore supported a partial-discharge investigation, while the fleet rule left the diagnosis open. Treating the failed ratio as grounds to rule out partial discharge would have missed the winding defect later found on inspection.

How much acetylene could the reported zero conceal?
In June, 161 µL/L of methane divided by 1,456 µL/L of hydrogen put the sample within the fleet study’s limit of 0.2. The remaining condition involved acetylene and ethylene. Dividing the printed values gives 0/1, apparently within the 0.1 limit. Whether the measurement supports that conclusion depends on what the laboratory meant by zero.
Suppose the certificate had said “acetylene below 0.5 µL/L”. Taking the ethylene result of 1 µL/L as exact for the moment, acetylene concentrations of 0.05 and 0.3 µL/L would both fit that report. The first gives a ratio below 0.1 and the second a ratio above it. The 0.5 µL/L reporting limit is hypothetical. The published table does not give the actual limit.
I would ask the laboratory for the original certificate, the acetylene quantification limit for that ester, the convention for reporting values below it, and the uncertainty on ethylene at about 1 µL/L. Given a defensible upper bound for acetylene and a positive lower bound for ethylene, divide the former by the latter. A result at or below 0.1 supports the fleet criterion throughout the stated range.
With headspace analysis, the instrument measures gas that partitions from the liquid into the gas phase in a sealed vial. That partition depends on the gas, the liquid and the extraction temperature. Clause 5.1 of IEC 63585 points to IEC 60475 for sampling and to Annex F of IEC 60567:2023 for gas analysis in liquids other than mineral oil. At these low concentrations, ask how the laboratory verified its calibration for acetylene in the ester concerned. IEC 60475 on sampling and IEC 60567 on extraction and analysis.
Where do clause 5.3 and Annex B fit?
For synthetic ester, Annex B.2 and Table B.4 give percentiles for individual gas concentrations. Clause 3.1.8 explains the grounds for investigating an exceedance. Separate percentiles for methane and hydrogen cannot determine the percentile of their ratio. The relevant text for partial-discharge ratios is clause 5.3.2, read with clauses 5.3.1 and 5.3.6. The free edition preview identifies those sections but gives insufficient detail to apply all their numerical conditions to these samples. The values 0.2 and 0.1 above belong to the fleet study. IEC 63585 edition 1 preview, contents and definitions (PDF).
Why request an electrical partial-discharge test?
In 2025, Huijuan Wang and colleagues produced partial discharges in KI50EX synthetic ester and sampled the same experiment at 30, 60, 90 and 120 minutes. The three-ratio method they tested classified all four samples as overheating below 150 °C. The researchers knew the diagnosis was wrong because they controlled the applied stress. Repeating the same diagnosis four times tells us little about laboratory repeatability or diagnostic accuracy. KI50EX experiment, Tables 1 and 2.
In a study published on 20 November 2026, Xuelei Wang and colleagues recorded electrical pulses alongside gas measurements. Under moderate-energy discharge, hydrogen and carbon monoxide predominated in FR3 and MIDEL 7131. When the discharge shifted to intermittent sparking, the hydrogen and acetylene generation rates became more similar across the two esters and the reference mineral oil. Recording the pulses against the phase of the applied voltage gave the researchers an independent indication of when the discharge regime had changed. Comparative discharge experiments in Processes.
For the 20 kV transformer I would have requested electrical partial-discharge testing in April. Hydrogen warranted investigation and the triangle pointed to an electrical fault. The June result strengthened the case for investigating and changed the methane-to-hydrogen ratio. Retrieving the laboratory certificate could have settled the acetylene question. Locating the discharge took a different kind of evidence.
The IEEE account covers two transformers. Its authors report partial discharge in the windings and deposits of a waxy material known as X-wax. The affected windings were replaced. Both units returned to service without the previous excessive gassing. It was the investigation of the equipment that finally identified the component involved.
Natural esters at 120 °C: why the same ratio can move 161-fold
Clause 4.1.4 of IEC 63585 describes a test in which soybean ester and high-oleic sunflower ester were held at 120 °C for 164 hours. They produced nearly the same amount of ethylene, 7 and 8 µL/L respectively. Ethane was another matter: 563 µL/L in the soybean ester and just 4 µL/L in the sunflower ester. The resulting ethylene-to-ethane ratios were about 0.0124 and 2. The temperature was identical.
The soybean liquid contained 7% linolenic acid, compared with 0.2% in the sunflower liquid. The standard identifies oxidation of polyunsaturated constituents as a likely explanation for the gassing observed. On a soybean-ester transformer, I would compare ethylene with earlier samples and with the load history before downgrading a suspected thermal fault on the ratio alone. A high ethane background can keep the ratio low even as ethylene rises. Further reading on DGA in ester-filled transformers.