Is the oil fit for service?

Compare the oil tests with the limits for the fluid, lifecycle state, equipment and voltage. Each property is rated on its own, and the headline points to the worst one.

It runs in your browser: nothing you enter leaves your device, and no account is needed.

Insulating Fluid ConditionFree · v1.0.9

What goes in

  • Oil test results: breakdown voltage, water, acidity, dissipation factor, interfacial tension
  • Fluid, lifecycle state, equipment and voltage class

Standards

  • IEC 60422:2024 · IEC 60422:2013 (withdrawn, for comparison) · IEEE C57.106-2015

What comes out

  • Each property against its limit
  • The property that sets the headline
  • The edition used, named

Insulating Fluid Condition

Enter your values

Accept the tool's conditions inside the frame, then type or paste your values. The result appears in the same frame.

After the result

Email me a copy of this result

The copy is the result shown in the frame, sent once to your address with the tool name and version. Seetalabs keeps no copy of your values.

How it is calculated

Method, standards and worked examples

Every result names the method and the edition it rests on. The detail is here, section by section.

How it works, step by step
  1. Describe the liquid and its use. Choose the fluid (mineral oil, natural ester from soybean, rapeseed or sunflower, synthetic ester, or silicone), the standard and the lifecycle state: in service, as delivered, or after filling, where the standard publishes that state. Then choose the equipment (main tank, on-load tap-changer, switchgear, bushing or instrument transformer) and enter Um.
  2. Check the table the tool will use. A short chain, "Which table of limits applies", goes from the liquid to the standard, the state, the equipment and Um, and ends with the table and category in plain words. Options that change the limits, such as an inhibited oil or the tap-changer connection, sit just below it.
  3. Enter one or more samples. Each sample has a date, a temperature and the properties you have. Every property is optional: an empty field is not evaluated and never becomes zero. A value reported as below the detection limit, written "<x", is evaluated at x only where a lower value is better; elsewhere the row is shown as not classifiable.
  4. Read the result. Each property shows its band, its trend and the number of samples behind it. A summary gives the property that sets the headline, then a dossier answers the questions in order: is the liquid fit for service, which symptom groups appear, what to do and when, where the water is (oil or paper), how each property is moving, and how the same sample reads under the other in-service standards for that fluid.

You can save your inputs to a JSON file on your own computer, open it again later and print the result.

Method and standards

The limits come from the standard you select. For mineral oil the tool carries IEC 60422:2024, IEC 60422:2013 and IEEE C57.106-2015. For natural esters it carries IEC 62975:2021 and IEEE C57.147-2018; for synthetic ester, IEC 61203:2025; for silicone, IEC 60944:1988 and IEEE C57.111-1989. Each row cites the table and page it comes from, for example "IEC 60422:2024 Table 5, Cat A, row BDV".

IEC standards give Good, Fair and Poor bands per property. The tool applies the edges as printed: the Good edge is strict and the Fair edge is inclusive. IEEE C57.106-2015 gives one continued-use limit per property, so the result is Class I, when every limit you entered is met, or "Not Class I". The standard assigns Class II or III on a composite evaluation (clause 4.2.1); the tool shows which properties fail and leaves that evaluation to you.

The headline is the band of the worst scored property. It points you to the property that needs attention first; it is not an overall verdict on the liquid, because the standards set limits and actions per property, not for the liquid as a whole.

Water is handled in three ways. For mineral oil sampled at 20 °C or above, the tool converts water content to 20 °C with IEC 60422:2013/COR1 Formula A.1. It converts water content to relative saturation and classifies it with IEC 60422:2013 Table A.1 for mineral oil, whichever IEC 60422 edition you chose, because the 2024 edition gives relative saturation classes only for online monitoring (Table B.1). Natural esters use IEC 62975:2021 Table A.2. Paper moisture in equilibrium with the oil is shown for information; Moisture & Loading Capability takes that question further.

Treatments follow the symptom groups of IEC 60422:2024 Table 10: physical, chemical, additives and corrosive sulphur. Re-inhibition is offered only for mineral oil and only when acidity and interfacial tension allow it. CIGRE TB 962 §5.7.7 adds an early-reclamation flag, for example at acidity of 0.10 mg KOH/g or more even while the band is still Good. For a passivated oil under IEC 60422:2013, a passivator loss above 10 mg/kg per year, computed from your samples, moves the row to Fair, as corrected by CIGRE TB 625. The next sample date comes from IEC 60422:2013 Table 4, with a confirmation sample when a property is Poor.

Trends are a Seetalabs® choice, declared on the page: a least-squares slope over the dated samples and a straight-line projection to the next band edge, never beyond 20 years.

Mineral-oil limits (IEC 60422:2024, IEC 60422:2013, IEEE C57.106-2015) and the synthetic-ester table of IEC 61203:2025 were checked cell by cell against the standards. For natural esters under IEC 62975:2021 and for silicone, the rows cite their table and clause and are marked as cited rather than checked. Where a band edge is our reading of the table, the row says so. The status is shown in the information panel of each row.

Worked example: one sample, three standards

The example ships with the tool. A generator step-up transformer, mineral oil, inhibited, main tank, Um 245 kV, sampled four times between 2020 and 2026. The latest sample, taken on 14 April 2026 at 52 °C, reads:

Property Value
Breakdown voltage 58 kV
Water content 16 mg/kg
Acidity 0.13 mg KOH/g
Dissipation factor at 90 °C 0.13
Interfacial tension 23 mN/m
Colour 3
Oxidation inhibitor remaining 22 % of the original content

Under IEC 60422:2024, the tool selects Table 5, Category A. The headline is Poor, set by the oxidation inhibitor: 22 % is below the 40 % edge of the Fair band. Breakdown voltage, water, acidity, dissipation factor, interfacial tension and colour are all Fair. Across the four samples, interfacial tension is falling and reaches Poor within two years on the current slope, and water has risen. The treatment suggested for the chemical symptoms is reclamation, then re-inhibition; reconditioning alone is not suggested. Because one property is Poor, the next step is a confirmation sample.

Under IEC 60422:2013, the headline is again Poor on the inhibitor. Colour is shown but not scored, because this edition treats it as a qualitative property.

Under IEEE C57.106-2015, for 230 kV and above, the result is "Not Class I". Acidity of 0.13 mg KOH/g, Fair under IEC 60422:2024, exceeds the IEEE continued-use limit of 0.10, and interfacial tension of 23 mN/m is below the IEEE limit of 32.

The same sample is Poor under one standard because of the inhibitor, and Not Class I under another because of acidity and interfacial tension. The tool shows all three readings side by side, with the table behind each one, so the choice of standard is visible in the result rather than hidden in it.

A check you can repeat by hand: 10 mg/kg of water measured at 40 °C corresponds to about 4.5 mg/kg at 20 °C with IEC 60422:2013/COR1 Formula A.1, the example given in the standard.

Free tools: scope and conditions of use

What the furans say about the paper: Paper Insulation Remaining Life: Paper Insulation Remaining Life. Several transformers and several laboratories? RONIN reads the reports you already receive.